Close Menu

Solenoid Valve Mechanics: Understanding Force Balance Equations


 

When evaluating a solenoid valve for a particular application, it is important to ensure that the valve can both remain in state and transition between its de-energized and fully energized states under all potential operating conditions. To accomplish this, a design engineer must identify all forces that will be applied to the valve components over its intended life cycle. They must also determine the worst-case conditions associated with each force both during each state and throughout any transition between states.

By calculating the combination of forces using a force balance equation, an engineer can determine if the valve will behave as intended. The design should include a margin of safety above the worst-case scenario due to potential tolerances associated with different forces. The factor of safety above the force margin may need to be more significant in the following scenarios: if the combination of forces are more complex, if there is a higher potential for failure, or if the result of failure is more severe.

 

What Forces Impact the Performance of a Solenoid Valve?

There are several forces at play within a solenoid valve that must be controlled to ensure consistent operation. While these forces are generally present in every solenoid valve, the specific configuration, environment, and function of the valve will determine the level of impact that each force has on operation. When evaluating whether a solenoid valve will function properly within a system, the following forces must be considered:

  • Solenoid Coil Force: The solenoid coil is the primary force that can be applied and removed by the user’s control system. The coil must be appropriately sized so that it can overcome all forces working against it, yet must not be so large that it is cumbersome to design into systems or consumes too much power.
  • Spring Force: Most solenoid valves utilize a spring to return the armature to its de-energized position. Some solenoid valves incorporate multiple springs to assist or mitigate the coil force and to position other components within the valve during various conditions.
  • Fluid Pressure Force: Both static and dynamic pressures must be considered. This includes pressures across a range of operating conditions and during all states as the valve translates from one position to the other (e.g., energized to de-energized or de-energized to energized). Depending on the configuration of the valve, the fluid may travel through multiple individual restrictions across different subcomponents and passageways. The pressure differentials across these individual restrictions result in forces that impact the transition of the valve. In configurations with more complex multi-component valve designs, these calculations can become more complicated but are critical to ensuring valve performance.
  • Friction: Sliding fits are common as the plunger and other subcomponents transition from one position to another. Consideration must be given to the resulting friction forces acting on the components.
  • Stiction: Materials used to create seals within a solenoid valve exhibit static friction – especially elastomers. Depending on the material, fluids, temperature, and time of contact, the force of stiction can have a substantial impact on valve performance.
  • Residual Magnetism: Solenoid coils are inductive and therefore resistant to changes in current through the coil. When power is removed from the solenoid coil, some magnetic force still exists but dissipates rapidly afterwards.
  • Environmental Forces: External environmental forces such as gravity, shock, or vibration may be applied to the solenoid valve. For example, a solenoid valve may operate in a handheld device that can be dropped or in a vehicle that vibrates extensively. While evaluating force balance equations, these forces should be considered along with the potential failure mode associated with shock or vibration. It is notable that Force (F) = Mass (M) * Acceleration (A). If these external forces include high acceleration but are acting on a subcomponent of extremely low mass, the total force may still be insignificant when compared to the coil, spring, or fluid pressure forces.

 

Basic Force Balance Equations: Sample Scenario

The following scenario helps to explain how an engineer would go about designing a solenoid valve capable of achieving the required force margins based on system requirements and a known valve layout.

In Figure 1, a solenoid valve is required to operate in a system with pressure ranging from 800 to 1000 psia at port P1 venting to the atmosphere at P2. Port P1 has a diameter of 0.025 inches. During a worst-case scenario, the solenoid valve is subjected to a shock equivalent to 50G applied against 0.5 grams of mass in any direction. The force of friction (F5) is a maximum of 0.005 lbf. The forces associated with stiction (F6) and residual magnetism are negligible.

QUESTION ANSWER
1. What force must the spring apply to ensure the valve stays closed during the worst-case condition with a factor of safety two times the force? The force of fluid pressure will work against the force of the spring. In the worst-case condition, we will use the highest operating pressure. The force of the shock will be assumed in the opposite direction of the spring and work against it. To stay closed, the valve will remain in a static position, and the force of friction will not apply.
FSpring (F4) = Factor of Safety * (ForceP1 + ForceShock)
ForceP1 (F1) = Pressure * Area = 1000 * (π * (0.025/2)2) = 0.491 lbf
ForceShock = 0.5 grams * (1 lb / 453.6 grams) * 50 G = 0.055 lbf
FSpring = 2 * (0.491 lbf + 0.055 lbf) = 1.092 lbf
2. Using the calculated spring force, what is the required coil force (F3) to open the valve with a 1.5 factor of safety under the worst-case condition? The force of the spring is working against the force of the solenoid coil (F3). For the valve to open, the force of friction will apply and work against the coil. The fluid pressure is applying force to aid the coil. For a worst-case condition, we will use the lowest operating pressure acting on the smallest valve seat area. We will assume the valve is closed and the plunger is the furthest distance from the pole. The force associated with a shock is not considered in this calculation because a shock only occurs momentarily.
FCoil = Factor of Safety * (FSpring + ForceFriction – ForceP1)
FSpring = 1.092 lbf (from question 1)
ForceFriction (F5) = 0.005 lbf
ForceP1 = Pressure * Area = 800 * (π * (0.025/2)2) = 0.393 lbf
FCoil = 1.5 * (1.092 lbf + 0.005 lbf – 0.393 lbf) = 1.056 lbf

 

How Can You Increase the Strength of a Magnetic Field?

System operating conditions help dictate fluid pressure force and the intended end use impacts the resulting environmental forces applied to the solenoid valve. The above scenario represents a typical exercise that an engineer might work through when tailoring a common valve design for a unique system.

A pre-existing valve design will have known forces associated with stiction from the valve seal or friction from the movement of internal components. The spring is designed at a force necessary to hold the components in place while the valve is de-energized. The solenoid coil must then be designed to overcome the forces acting upon the plunger. There are several ways to increase the strength of the magnetic field:

  • Current: Increasing the current through the wire will increase the magnetic field. This can be accomplished by increasing the voltage applied from the power supply, or by decreasing resistance of the coil (see Ohm’s Law). The resistance of the coil can be changed by using a different gauge of wire or changing the material properties of the wire.

    Ohm’s Law

    V (voltage) = I (current) * R (resistance)

    Based on this law of physics, increasing voltage or decreasing resistance will increase current.

  • Number of Turns: Increasing the number of turns on the coil per unit of length helps to increase the size of the magnetic field. The number of turns will influence the coil resistance and package size.
  • Electromagnetic Core: Placing an iron core inside the coil concentrates the magnetic field to the center of the coil. Concentrating the field at the center of the coil provides more force to move the plunger. This can be accomplished by constructing the bobbin out of iron.
  • Coil Cover: To further concentrate the magnetic field of the solenoid coil, the cover may also be manufactured out of material that assists in directing the magnetic field.

Force balance equations are important to determine if a solenoid valve is appropriate for its application. As the number of ports, flow paths, and operating conditions become more complex, so do the calculations necessary to develop the valve.

 

How Can The Lee Company Help?

The Lee Company designs and manufactures a wide range of valves from miniature plastic pneumatic solenoid valves intended for respiratory therapy applications to high-pressure high-temperature hydraulic solenoid valves used in aircraft, rockets, and satellites operating miles above us. If you are searching for a valve to meet your needs and would like to learn more about solenoid valves offered by The Lee Company, click here or contact a Lee Sales Engineer today.

If you want to learn more solenoid basics, review our related insights below.

RELATED INSIGHT

WHAT'S NEW

ENGINEERING NEWS FROM THE LEE COMPANY

From emerging news to helpful resources and industry insights, we’re here to help you stay up to date on everything fluid control.